The four systems, and where each locks
SSEMCO makes four locking systems for IEC 60320 cords, and they lock at different ends. P-Lock and P-Lite lock the plug into the PDU outlet — and only into an outlet built for it. S-Lock locks the connector onto the equipment inlet, and any standard inlet will do. D-Lock puts one of each on the same cord. Every figure and every compatibility claim below comes from the maker's or the PDU maker's own publication; the sources are listed at the end.
| System | Locks at | Needs on the PDU side | Needs at the equipment | Published retention |
|---|---|---|---|---|
| P-Lock | PDU outlet | A P-Lock-ready outlet (latch slots for the tabs) | Nothing — a standard C13, C15 or C19 connector | Up to 120 N (about 27 lbf) — SSEMCO |
| P-Lite | PDU outlet | A P-Lock-ready outlet | Nothing — a standard C13 | The same latch as P-Lock; no separate figure published |
| S-Lock | Equipment inlet | Nothing — a standard C14 or C20 plug | Any standard C14 or C20 inlet | Not published by SSEMCO |
| D-Lock | Both ends | A P-Lock-ready outlet | Any standard inlet | P-Lock end up to 120 N; S-Lock end not published |
P-Lock
The most widely deployed locking plug in the rack.
How it works: two spring tabs — the P-shaped clips — on either side of the plug head click into the latch slots of a P-Lock-ready outlet as the plug seats. Pull on the cord and the tabs bear on the outlet, not the pins. Pinch both tabs and pull to release. On a plain outlet with no latch slots the plug seats and carries current like any C14 or C20, but it does not lock; SSEMCO calls that "backward compatible with any standard C13 outlet". The connector at the equipment end is a standard C13, C15 or C19 and locks nothing.
Withdrawal force: up to 120 N (about 27 lbf), SSEMCO's published figure.
| Attribute | Detail |
|---|---|
| Plug end (PDU side — the end that locks) | C14 for C13 outlets, C20 for C19 outlets |
| Connector end (equipment side — standard, does not lock) | C13 (10 / 15 A), C15 (for 120 °C inlets), C19 (16 / 20 A) |
| Colours | Black, blue and red from stock; other colours to order |
| PDU outlets it locks into | P-Lock-ready outlets: Server Technology (lockable, HDOT and HDOT Cx), Raritan PX (SecureLock-ready — Raritan's own SecureLock cords are P-Lock plugs), Vertiv / Geist (high-retention colour-coded and Combination C13/C19 outlets), Eaton G4 (P-Lock C13 / C19 / C39 outlets, Tripp Lite series), GELU |
Best for: the PDU end must not come loose and the PDU is one of the makers above. If the PDU has plain outlets, P-Lock only seats — choose an equipment-side lock (S-Lock, A-Lock) or a cord that locks both ends on plain hardware (Z-Lock+) instead. P-Lock cords →
P-Lite
P-Lock for high-density PDUs.
How it works: the P-Lock latch on one side of a low-profile C14 plug head whose other side is recessed, so a fingertip reaches the single tab between neighbours on a fully loaded PDU. Press the tab into the recess and pull to release. Same P-Lock-ready outlets as P-Lock; Eaton sells the same idea for its G4 PDUs as P-Lock Lite.
Withdrawal force: the same latch as P-Lock; SSEMCO publishes no separate figure for P-Lite.
| Attribute | Detail |
|---|---|
| Plug end (PDU side — the end that locks) | C14 only, for C13 outlets |
| Connector end (equipment side — standard) | C13 |
| Cordage | Slim 18 AWG SVT, to keep the bundle thin in a dense row |
| PDU outlets it locks into | The same P-Lock-ready outlets as P-Lock |
Best for: outlets on a pitch so tight that a full-size P-Lock head blocks its neighbour. P-Lite cords →
S-Lock
The rotary lock for the equipment end.
How it works: SSEMCO's second-generation rotary securing system. Push the connector onto the inlet and turn the grey collar a quarter turn; internal pins pinch the inlet's pins. Turn the collar back and pull to release — one hand, no clearance needed beside the connector, which is why it suits inlets packed shoulder to shoulder. It fits any standard C14 or C20 inlet; nothing on the PDU side matters, because the plug end is a standard, non-locking plug. It is not Scolmore's IEC Lock (a C13 with a red top tab that grips the earth pin): a different maker and a different mechanism.
Withdrawal force: SSEMCO publishes none for S-Lock, so this guide prints none.
| Attribute | Detail |
|---|---|
| Connector end (equipment side — the end that locks) | C13, C15, C19 |
| Plug end (PDU side — standard, does not lock) | C14 and C20 from stock; NEMA and hospital-grade plugs to order |
| Ratings | 10 / 13 / 15 A 250 V (UL), 10 A (VDE); −25 °C to +70 °C |
| Inlets it locks onto | Any standard IEC 60320 C14 or C20 inlet, on any equipment |
Best for: the equipment must not come unplugged, the PDU is anything at all, and a twist release is preferred to squeeze tabs. S-Lock cords →
D-Lock (Dual-Lock)
Both ends locked.
How it works: a P-Lock plug for the PDU and an S-Lock connector for the equipment, on one cord. Pinch the plug tabs at the PDU; turn the collar back at the equipment — two different motions on purpose, so freeing one end does not free the other by reflex. The plug end needs the same P-Lock-ready outlets as P-Lock; on a plain outlet it seats without locking and the cord behaves as an S-Lock.
Withdrawal force: up to 120 N at the P-Lock end (SSEMCO); none published for the S-Lock end.
| Attribute | Detail |
|---|---|
| Plug end (PDU side) | C14 P-Lock, C20 P-Lock |
| Connector end (equipment side) | C13, C15 or C19 S-Lock |
| Colours | Black, red and blue |
| PDU outlets it locks into | P-Lock-ready outlets: Server Technology, Raritan, Vertiv / Geist, Eaton G4, GELU |
Best for: racks where neither end may come loose and the PDU has P-Lock-ready outlets. For plain PDU outlets at both ends the answer is Zonit's Z-Lock+, which we build in Connecticut. Dual-Lock cords →